Description
DC (Deep Cycle) series is specially designed for frequent cyclic discharge. By using strong grids and specially designed active material, the DC series battery offers 30% more cyclic life than the standby series. It is suitable for UPS, solar & wind energy, telecom system, electric power system, electric vehicles, golf cars, etc.
Specification
Cells Per Unit | 6 |
Voltage Per Unit | 12 |
Capacity | 200Ah@10hr-rate to 1.80V per cell @25℃ |
Weight | Approx. 60.0 Kg (Tolerance±1.5%) |
Max. Discharge Current | 2000A (5 sec) |
Internal Resistance | Approx. 4 mΩ |
Operating Temperature Range | Discharge: -20℃~60℃ Charge: 0℃~50℃ Storage: -20℃~60℃ |
Normal Operating Temperature Range | 25℃±5℃ |
Float Charging Voltage | 13.6 to 13.8 VDC/unit Average at 25 C |
Reference Capacity | C3 136.5AH C5 151.5AH C10 174.0AH C20 200.0AH |
Recommended Maximum Charging Current | 60 A |
Equalization and Cycle Service | 14.6 to 14.8 VDC/unit Average at 25 C |
Self Discharge | RITAR Valve Regulated Lead Acid (VRLA) batteries can be stored for up to 6 months at 25℃ and then recharging is recommended. Monthly Self-discharge ratio is less than 3% at 25℃.Please charged batteries before using. |
Terminal | Terminal F10/F16 |
Container Material | A.B.S. UL94-HB, UL94-V0 Optional. |